Delivered capacity · Distribution · Tool
What compression actually costs a flex runout
Squeezing flexible duct does not cost you a little airflow. A five percent compression ratio roughly doubles the friction loss. Fifteen percent roughly quadruples it. This calculator runs the ASHRAE procedure and shows every intermediate number, so you can check the arithmetic rather than take the answer on faith.
Calculator
Flex duct friction loss and carrying capacity
Enter one duct run. The tool computes the friction loss fully extended, applies the published compression correction, and compares both against the pressure budget you have available. Round metal pipe of the same diameter is shown alongside for reference.
LBNL measured 6, 8 and 10 in. The 7 and 9 in. correction factors are interpolated between measured points. Sizes below 6 in. have no published correction factor and are not offered.
Runouts on four New Orleans Manual D reports ran 12 to 84 ft, with most between 12 and 35 ft.
The fraction of length squeezed out of the duct: 25 ft of flex stuffed into a 21 ft, 3 in. span is 15 percent. Zero means pulled taut and supported.
The design friction rate on all four reports reviewed. It is also the Rhvac default, so read it as standard practice rather than as four independent judgments.
Fan external static pressure minus coil, filter and accessory losses. On the one report carrying full fan data: 0.60 less 0.36 leaves 0.24.
Supply plus return effective length of the critical path, read off your own report. The tool does not invent fitting equivalent lengths.
0.098 in. w.c. / 100 ft
- Velocity
- 573 fpm
- Reynolds number
- 39,300
- Friction factor f
- 0.0318
- Velocity pressure
- 0.0205 in.
- Friction rate, taut
- 0.098 in./100 ft
- Compression correction
- 1.00 ×
- Total loss over run
- 0.024 in. w.c.
- Allowable friction rate
- 0.100 in./100 ft
Method and provenance
- Friction loss of fully extended flex from the Darcy-Weisbach equation
Δp = f · (12L/D) · pv, with f from Colebrook-White andpv = ρ(V/1097)²at standard air, ρ = 0.075 lbm/ft³. - Absolute roughness
ε = 0.003 ft. ASHRAE Fundamentals Table 1 classes "flexible duct, nonmetallic and wire, fully extended" as medium rough at 0.003 ft, citing Abushakra et al. 2004 and Culp 2011. Older editions of the same table put all fabric-and-wire flex in the rough category at 0.01 ft; that classification has been superseded, which is why design software still carrying 0.01 for runouts disagrees with this tool. - Compression enters as a pressure drop correction factor multiplying
the result of step 1 — the application the
ASHRAE Duct System Design Guide
specifies. Slopes in
PDCF = 1 + a·rcare a = 25.35 at 6 in., 21.61 at 8 in. and 16.18 at 10 in., from Abushakra, Walker and Sherman, "Compression Effects on Pressure Loss in Flexible HVAC Ducts" (LBNL, 2004). - Carrying capacity is solved by bisection on airflow until the friction rate meets the
allowable rate —
100 × ASP ÷ TEL, the standard Manual D relationship.
What this tool refuses to do. It does not model compression by inflating
roughness. Compression is a measured multiplier on pressure drop, and an expression like
ε = 0.003 × (1 + k·compression) hides an invented coefficient inside a
physical-looking constant. It does not use ACCA Manual D Appendix 17 correction figures,
which are paywalled and reach the public only through secondary characterization. It does
not supply fitting or boot losses from a private table; those enter only as a total
effective length you read off your own report.
Limits. Straight horizontal runs only — no sag, no bends, no fittings, which means real installations lose more than this predicts, not less. The correction factors are measured at three diameters; 7 and 9 in. are interpolated and nothing is extrapolated past 10 in. or below 6 in. The linear PDCF fit tracks the measured points closely up to about 15 percent compression; at 30 percent it runs above the measured 8 in. value, so treat the high end of the slider as the published fit rather than a measured point. The velocity ceilings and the 0.10 in. w.c./100 ft design rate are conventional practice and also the defaults in the software that produced the reports behind them.
This is deliberately a conservative calculation. When the tool shows a problem, the real run is probably worse, not better, for three reasons:
- It models one straight, fully supported run. Sag, bends, kinks, crowded plenum takeoffs, boots and fittings all add resistance that the tool does not count.
- It starts from the most favorable roughness for fully extended flex, the current
ASHRAE value of
ε = 0.003 ft, not the older 0.01 ft that some design software still carries for runouts. - It ignores leakage. Air that escapes through unsealed collars, wyes and boots never reaches the room, and none of it is subtracted here.
One choice runs the other way, and it is stated above: at the high end of the slider the published linear fit gives more loss than LBNL measured for 8 in. duct. Up to about 15 percent compression, fit and measurement agree closely.
So the tool is good for showing that a run is starving a room. It is not a tool for proving an existing system is adequate. That takes measured static pressure and measured room airflow.
Written and maintained by Jeff Haag, who installs insulation and designs duct systems in New Orleans for a living. Default values were calibrated against four ACCA-approved Manual J/D reports for Gulf Coast homes; those reports are private and no figure from any individual house appears here. If you want this run against your own measured static pressures and effective lengths rather than against defaults, that is a job for a consult, not for a web form.
Why the numbers look so brutal
An 8 in. flex runout pulled taut carries about 202 CFM at a 0.10 in. w.c./100 ft design rate. Compress that same duct 15 percent and the correction factor is 4.24, which drops it to about 95 CFM — less than half the air, at the same pressure budget, through the same duct.
That is the mechanism behind most of the "the new system still doesn't cool the back bedroom" calls. Nobody undersized the duct on paper. The duct was sized taut and installed slack, and no amount of equipment upsizing fixes a runout that is throwing away three quarters of its capacity to a geometry problem.